Caribbean & Central America
Selective — see noteIndustrial cooling & ventilation for Honduras
The apparel maquila belt running north from San Pedro Sula through Choloma and Villanueva to Puerto Cortés is one of the largest concentrations of garment manufacturing in the Americas, and the sewing floors in it are the clearest use case we have anywhere in Central America. Ayzair supplies HVLS fans for floor-level air movement over the lines, hammer wall exhaust fans for roof heat, and inline duct fans for pressing and finishing extraction. Everything is built to order on the voltage and frequency the plant actually runs.
Climate suitability — the honest version
32–35 °C in the Sula valley and on the Caribbean coast with 70–85% afternoon humidity through most of the year
Evaporative cooling is the wrong product for Honduras and we say so plainly. The Sula valley and the Caribbean littoral are humid enough through the afternoon that a cooler cannot generate a useful temperature drop — it mostly adds water to air that is already carrying it. The genuine case here is large and it is air movement: garment floors in San Pedro Sula, Choloma and Villanueva are long, crowded and hot, and HVLS fans over the line with hammer wall exhaust fans pulling roof heat out is a well-proven combination in exactly that building type.
Puerto Cortés
Primary destination port
35–45 days
Sea transit from India
10–20days
Production lead time
4terms
EXW · FOB · CIF · CFR
The complete range
All six Ayzair families, supplied to Honduras.
Every product we make is available in Honduras — thirty-four models across six families. They are ordered here by how well each one suits the local climate and the industries that dominate this market, but nothing is off the list.
Industries
Who buys from us in Honduras.
Logistics & compliance
Shipping to Honduras.
| Destination ports | Puerto Cortés |
| Sea transit | 35–45 days from Nhava Sheva, transhipped at Caucedo, Kingston or Manzanillo |
| Incoterms | EXW · FOB · CIF · CFR |
| Container loading | 40 ft HQ: HVLS fans ship knocked down, typically 12–18 fans depending on diameter |
| Production lead time | 10–20 working days |
- Honduran supply is 110 V / 220 V single phase and 220 V or 440 V three phase at 60 Hz. Run a 50 Hz motor on 60 Hz and it turns roughly 20% faster — more current, more heat, more noise, and bearings and impellers that are not rated for the speed. We wind for 60 Hz when the order states it, so give us the frequency and voltage with the enquiry.
- Sewing floor heights vary a great deal in the Sula valley. HVLS fans need 7 m of clear height below the structure; plenty of older maquila sheds are 5–6 m and for those we quote hammer wall exhaust fans and mobile fans instead rather than selling a fan that cannot work in the room.
- Puerto Cortés is the practical entry point for the whole Sula valley and the inland haul is short. Hurricane season from June to November does affect sailing schedules into the Gulf of Honduras — plan dates with that in mind rather than against a best-case transit.
Honduras enquiry
Get a proforma invoice for Honduras.
Tell us the models and quantities, or just describe the building and let us size it. You will receive USD pricing, your Incoterm, a container loading plan and a confirmed lead time — within one working day.
Export desk
Answers
Supplying Honduras — common questions
Cannot find what you need? Call +91 80871 10156 or WhatsApp us — an engineer, not a call centre, picks up.
Ask on WhatsAppHow many HVLS fans does a typical sewing floor need?
It depends on the clear height and the obstruction above the lines, but as a working figure a 24 ft fan covers a broad circle of floor and plants usually space them down the length of the hall rather than clustering them. Send us the floor dimensions, the clear height under the lowest obstruction and the line layout and we will mark up a spacing drawing before you commit to a count.
Can evaporative coolers reduce the temperature on a garment floor in San Pedro Sula?
No, not meaningfully. The Sula valley is humid through the afternoon and evaporative cooling depends on dry air. You would be adding humidity to a room where operators are already working in it. HVLS fans move air across people at low energy cost and exhaust fans remove the heat that collects at roof level — that pairing is what actually changes conditions on that floor.
Do your motors come wired for 220 V three phase?
They are built to order, so yes — tell us 220 V or 440 V three phase at 60 Hz and the motor is wound and wired for it before it leaves Pune. We do not ship a 50 Hz unit and expect your electrician to compensate for it.
Next step
Shipping to Honduras?
Send your requirement and we will confirm the freight route, transit time, landed cost and whether our products genuinely suit your climate — before you commit.