Caribbean & Central America
Selective — see noteIndustrial cooling & ventilation for Guatemala
Guatemalan industry concentrates along the CA-9 corridor out of Guatemala City — Zona 12, Villa Nueva, Amatitlán and on down to Escuintla and Puerto Quetzal — with a second cluster around Santo Tomás de Castilla on the Caribbean side. Ayzair supplies HVLS fans, hammer wall exhaust fans and mobile fans to maquila floors, food plants, cement works and coffee mills in those areas. Equipment is built to order so the motor matches Guatemalan supply rather than being adapted after it lands.
Climate suitability — the honest version
32–35 °C on both coastal plains with 70–85% afternoon humidity; a genuine dry season November–April and distinctly drier air in the highlands above 1,500 m
Evaporative cooling is the wrong product for most of Guatemala and we will not sell it as if it were. On the Pacific and Caribbean lowlands afternoon humidity sits at 70–85% for most of the year, which leaves almost no wet-bulb depression to work with — a cooler there adds moisture and very little temperature drop. What does work is moving air and getting roof heat out: HVLS fans where the clear height allows, hammer exhaust fans where it does not. The dry corridor and the highlands are a real exception and we treat them as one.
Puerto Quetzal
Primary destination port
35–45 days
Sea transit from India
10–20days
Production lead time
4terms
EXW · FOB · CIF · CFR
The complete range
All six Ayzair families, supplied to Guatemala.
Every product we make is available in Guatemala — thirty-four models across six families. They are ordered here by how well each one suits the local climate and the industries that dominate this market, but nothing is off the list.
Industries
Who buys from us in Guatemala.
Logistics & compliance
Shipping to Guatemala.
| Destination ports | Puerto Quetzal · Santo Tomás de Castilla |
| Sea transit | 35–45 days from Nhava Sheva, normally transhipped at Balboa, Manzanillo or Caucedo |
| Incoterms | EXW · FOB · CIF · CFR |
| Container loading | 40 ft HQ: HVLS fans ship knocked down at high density · up to 60 coolers |
| Production lead time | 10–20 working days |
- Guatemalan supply is 120 V / 240 V single phase and 240 V or 480 V three phase at 60 Hz. A 50 Hz motor run on 60 Hz turns roughly 20% faster — it draws more current, runs hotter and noisier, and the bearings and impeller are not rated for that speed. We wind motors for 60 Hz when the order states it, so tell us the frequency and voltage at enquiry and nothing has to be improvised on site.
- The Pacific dry corridor and the highlands above 1,500 m do have a real dry season from November to April, and portable evaporative coolers have a narrow seasonal use there. It does not change the verdict for the coast or for year-round plant cooling.
- Puerto Quetzal handles the Pacific traffic and Santo Tomás de Castilla the Caribbean; tell us which one suits your broker before we book, because the transhipment route and the inland haul differ substantially.
Guatemala enquiry
Get a proforma invoice for Guatemala.
Tell us the models and quantities, or just describe the building and let us size it. You will receive USD pricing, your Incoterm, a container loading plan and a confirmed lead time — within one working day.
Export desk
Answers
Supplying Guatemala — common questions
Cannot find what you need? Call +91 80871 10156 or WhatsApp us — an engineer, not a call centre, picks up.
Ask on WhatsAppWould evaporative coolers work in our Escuintla plant?
No, and we would rather say so now. Escuintla sits on the humid Pacific plain where afternoon relative humidity runs 70–85% for most of the year. Evaporative cooling needs dry air to produce a temperature drop; in that humidity you get moisture and noise instead of cooling. HVLS fans and hammer wall exhaust fans are the right answer there, and they cost less to run.
Our shed in Villa Nueva is about 6 m to the roof steel — can we use HVLS fans?
Not well. HVLS fans need 7 m of clear height to develop the floor-level column of air they are designed for; below that the air hits the floor too close to the fan and the coverage collapses. At 6 m we would quote hammer wall exhaust fans to pull heat out of the roof, with mobile Model 1500 fans for spot cooling at workstations.
Do you hold Guatemalan electrical approvals?
We hold no Guatemalan listing and will not claim one. We supply the full technical file — wiring diagrams, motor data, test reports and the CE and IEC documentation we do hold — and your importer or electrical contractor confirms what the local authority requires. If a buyer tells us an approval is expected, we will say plainly whether we can obtain it and what it adds in time and cost.
Next step
Shipping to Guatemala?
Send your requirement and we will confirm the freight route, transit time, landed cost and whether our products genuinely suit your climate — before you commit.