Americas
Selective — see noteIndustrial cooling & ventilation for Ecuador
The shrimp farms and processing plants around Machala, Durán and the Guayas estuary and the flower pack-houses at Cayambe and Tabacundo run halls where wash-down water, chilled rooms and hot afternoons all meet in the same building. Moving air across the floor and pulling the heat and humidity out at the wall is what those buildings need, not added moisture. Ayzair also ships into the Guayaquil banana and cement trades and up to the Quito industrial corridor, all from Pune via Guayaquil.
Climate suitability — the honest version
Coastal Guayaquil at 31–34 °C with 70–85% afternoon humidity; Quito at 2,850 m stays 19–22 °C all year
Evaporative cooling is the wrong product for the Ecuadorian coast. Guayaquil, Machala and Manta sit at 70–85% afternoon humidity through the hot season, and a cooler that works by evaporating water into that air has almost nothing to evaporate into — it will raise the moisture load and barely move the temperature. The honest case here is air movement and extraction: HVLS fans across a pack-house or warehouse floor and hammer exhaust fans clearing heat, steam and odour out of shrimp and flower processing halls. Quito and the sierra are mild enough year round that cooling is not really the question at all; air change and extraction are.
Guayaquil
Primary destination port
35–45 days
Sea transit from India
10–20days
Production lead time
4terms
EXW · FOB · CIF · CFR
The complete range
All six Ayzair families, supplied to Ecuador.
Every product we make is available in Ecuador — thirty-four models across six families. They are ordered here by how well each one suits the local climate and the industries that dominate this market, but nothing is off the list.
Industries
Who buys from us in Ecuador.
Logistics & compliance
Shipping to Ecuador.
| Destination ports | Guayaquil · Posorja |
| Sea transit | 35–45 days from Nhava Sheva via Panama or the Cape, transhipped |
| Incoterms | EXW · FOB · CIF · CFR |
| Container loading | 40 ft HQ: up to 24 crated HVLS fans · 20 ft: up to 90 wall exhaust fans depending on size mix |
| Production lead time | 10–20 working days |
- Ecuador runs at 60 Hz, 120/240 V single-phase and 208/480 V three-phase, and this matters more than any other line on this page. A motor wound for 50 Hz will turn roughly 20% faster on a 60 Hz supply. It moves more air, which sounds like a bonus, but it also draws more current, runs hotter, is noticeably noisier, and loads bearings and impellers beyond what they were rated for — on a fan, absorbed power rises steeply with speed. We wind motors for 60 Hz when the order states 60 Hz. Say it on the enquiry and it is built that way; do not assume a 50 Hz machine can simply be plugged in.
- Coastal salt air at Guayaquil, Posorja and Manta is hard on sheet steel and fixings. Specify the marine-grade finish and stainless fasteners at order stage — retrofitting corrosion protection after a season near the estuary is not worth the saving.
- Shrimp and flower pack-houses are wash-down environments with chlorinated water and frequent hosing. Tell us which fans sit in the wet zone so we can specify sealing and motor protection accordingly, and keep electrical terminations out of the spray path.
- Imported electrical goods are commonly subject to a local conformity assessment, sometimes with inspection before shipment. We hold no Ecuadorian approval and do not claim one. We supply the full technical file, motor nameplate data and test reports, and your customs agent confirms the current requirement.
Ecuador enquiry
Get a proforma invoice for Ecuador.
Tell us the models and quantities, or just describe the building and let us size it. You will receive USD pricing, your Incoterm, a container loading plan and a confirmed lead time — within one working day.
Export desk
Answers
Supplying Ecuador — common questions
Cannot find what you need? Call +91 80871 10156 or WhatsApp us — an engineer, not a call centre, picks up.
Ask on WhatsAppOur supply is 60 Hz. Can we run your standard 50 Hz fans?
Not without accepting real penalties, so tell us 60 Hz and we will wind it properly. A 50 Hz motor on 60 Hz turns about 20% faster: airflow goes up, but so does current draw, motor temperature and noise, and the bearings and impeller are then running above the speed they were rated for. On the fans where that matters most we build the 60 Hz winding from the start, which costs you nothing extra at order stage and avoids a shortened life.
Would evaporative coolers help in our Guayaquil plant?
No. At 70–85% afternoon humidity there is almost no wet-bulb depression to exploit, and the cooler would add moisture to a building that is already struggling with it. For Guayaquil we quote HVLS fans for air movement over the working floor and hammer exhaust fans sized to the roof heat and the process load, and we leave the coolers off the quotation.
Will HVLS fans fit a shrimp pack-house?
Only if there is 7 m of clear height under the blade, and plenty of pack-houses are lower than that. Send us a section or a measured height. Where the building is low we quote wall-mounted hammer exhaust fans and, for spot cooling on a manual line, the Model 1500 mobile fan at 38,000 m³/h on 370 W.
Next step
Shipping to Ecuador?
Send your requirement and we will confirm the freight route, transit time, landed cost and whether our products genuinely suit your climate — before you commit.