Skip to content
Ayzair
Engineering8 min read

How to Size an Inline Duct Fan: Diameter, Airflow and Static Pressure

Airflow alone will not select an inline fan. The number that decides whether it moves air or just makes noise is static pressure — and almost nobody is asked for it.

Published 5 November 2026 · Updated 5 November 2026 · Ayzair engineering team

Most inline duct fan enquiries arrive with one number: the airflow. A kitchen needs 1,800 m³/h, a basement car park needs 4,000, a plant room needs 600. It feels like enough information to quote against, and it is not.

A fan rated at 1,800 m³/h delivers 1,800 m³/h into free air — nothing attached to it. Put it in the middle of eighteen metres of duct with four bends and a grease filter and it will deliver a fraction of that. The duct fights back, and the measure of how hard it fights is static pressure. Get that wrong and you install a fan that runs, draws current, makes noise and moves almost nothing.

The duct diameter is usually decided for you

In a retrofit the duct already exists, so the fan has to match it. An inline fan is sized to sit in the line, and stepping up or down a size means transitions, which cost pressure and make noise. Measure the existing duct's internal diameter before anything else.

On a new installation the diameter comes from air velocity. Keep it between 5 and 8 m/s for general extract: below that the ducts get needlessly large and expensive, above it the system starts to whistle and the pressure loss climbs sharply. A quick check — airflow in m³/h, divided by 3,600, divided by the duct's cross-sectional area in m², gives velocity in m/s.

Duct sizeAreaAt 5 m/sAt 8 m/s
Ø100 mm0.0079 m²140 m³/h225 m³/h
Ø150 mm0.0177 m²320 m³/h510 m³/h
Ø200 mm0.0314 m²565 m³/h905 m³/h
Ø250 mm0.0491 m²885 m³/h1,415 m³/h
Ø315 mm0.0779 m²1,400 m³/h2,245 m³/h

← Swipe the table sideways to see all columns

Static pressure: the number nobody is asked for

Static pressure is the resistance the fan has to push against, measured in pascals. Every metre of duct, every bend, every filter, grille and damper adds to it. Add them up and you get the operating point the fan actually has to work at.

You do not need a full calculation to get usefully close. Straight smooth duct at normal velocities costs roughly 1 to 3 Pa per metre. A 90° bend costs about the same as three to five metres of straight duct. A grease filter in a kitchen hood can be 50 to 150 Pa on its own, and more as it loads. A weather louvre at the discharge is typically 20 to 50 Pa.

Add a margin. Ducts get dirty, filters load up, and the figure you calculate on day one is the most favourable it will ever be. Thirty per cent on top of the clean figure is not pessimism — it is the difference between a system that still works in year three and one the maintenance team switches off.

ComponentTypical loss
Straight duct, smooth1–3 Pa per metre
Flexible duct3–6 Pa per metre
90° bend10–25 Pa each
45° bend5–12 Pa each
Grease filter, clean50–150 Pa
Weather louvre20–50 Pa
Backdraught damper15–40 Pa

← Swipe the table sideways to see all columns

Read the airflow at your pressure, not in free air

Every honest fan datasheet gives airflow at a stated pressure, and a curve showing how the two trade off. As pressure rises, airflow falls. A fan quoted at 2,300 m³/h is quoting its best case; the figure that matters is what it delivers at the pressure your duct imposes.

The Ayzair range is mixed-flow, which matters here. A mixed-flow impeller combines the pressure capability of a centrifugal fan with the air volume of an axial one, so it holds its airflow further up the pressure curve than a plain axial fan of the same diameter. That is why a Ø315 mixed-flow unit will still work on an eighteen-metre run where an axial fan of the same size would stall.

Each size is two-speed. The low setting is not a lesser product — it is the setting most installations should run at, with the high setting held in reserve for when the duct loads up or the design turns out to have been optimistic.

ModelDuctAir volume high / lowStatic pressure high / lowPower high / lowSound
AYZAIR-100Ø100 / 125200 / 150 m³/h180 / 130 Pa28 / 25 W30 / 25 dB
AYZAIR-150Ø150 / 160500 / 400 m³/h300 / 250 Pa50 / 40 W35 / 30 dB
AYZAIR-200Ø200850 / 700 m³/h350 / 280 Pa70 / 60 W50 / 45 dB
AYZAIR-250Ø2501,500 / 1,100 m³/h550 / 400 Pa170 / 130 W60 / 54 dB
AYZAIR-315Ø3152,300 / 1,800 m³/h700 / 500 Pa320 / 230 W66 / 61 dB

← Swipe the table sideways to see all columns

Worked example: a commercial kitchen extract

A kitchen hood needs 1,800 m³/h. The duct is Ø315, runs fourteen metres to the external wall, has three 90° bends, a grease filter at the hood and a weather louvre at the discharge.

Resistance adds up like this. Fourteen metres of straight duct at 2 Pa per metre is 28 Pa. Three bends at 20 Pa each is 60 Pa. The grease filter, clean, is 100 Pa. The louvre is 35 Pa. That is 223 Pa clean, and with a thirty per cent margin for a loaded filter and a dirty duct, call it 290 Pa.

So the requirement is 1,800 m³/h at roughly 290 Pa. The AYZAIR-315 delivers 1,800 m³/h at 500 Pa on its low setting, which clears 290 Pa comfortably and leaves the high setting — 2,300 m³/h at 700 Pa — in hand for when the filter loads. A Ø250 unit would have been the tempting cheaper choice, and at 1,500 m³/h maximum it would never have reached the required volume at all.

Three things that will catch you out

First, ambient temperature. A polypropylene-bodied fan is built for occupied spaces and normal plant rooms. If the fan sits somewhere genuinely hot — a roof void above a furnace, a duct carrying air off a process at 60 °C — a PP body is the wrong choice and we will say so rather than sell you one.

Second, supply frequency. Our motors are built for 50 Hz. On a 60 Hz supply a 50 Hz motor runs about twenty per cent faster, which raises airflow, current and noise together, and the bearings and impeller are not rated for it. The Philippines, most of the Americas, Saudi Arabia's western grid and parts of Japan are 60 Hz. Tell us the frequency and we will tell you honestly whether the fan suits.

Third, inlet. An extract fan can only remove as much air as the space can let in. If a sealed room has 1,800 m³/h pulled out of it and no deliberate inlet path, the fan is working against the whole building and will deliver far less than its rating. Make-up air is part of the design, not an afterthought.

Send us the duct, not just the airflow

Tell us the duct diameter, the run length, how many bends, what filters are in the line and your supply voltage and frequency. An engineer will return the model, the operating point and the delivered airflow you will actually get — within one working day, at no cost.

Get a fan selection

Answers

Related questions

Cannot find what you need? Call +91 80871 10156 or WhatsApp us — an engineer, not a call centre, picks up.

Ask on WhatsApp
What happens if I only tell the supplier the airflow?

You will be quoted a fan that produces that airflow in free air. Once it is installed in your duct the delivered volume will be lower — sometimes by half. Any supplier quoting an inline fan without asking about duct length, bends and filters is quoting a number, not a solution.

How do I estimate static pressure if I have no drawings?

Pace the duct run and count the bends. Multiply the length in metres by 2 Pa, add 20 Pa per 90° bend, add the filter and louvre losses from the table above, then add thirty per cent. That gets you close enough to select a fan with confidence. Send us those two numbers — metres and bends — and we will do the calculation for you.

Can an inline duct fan replace a different brand's unit?

Usually yes, if the duct diameter, airflow, static pressure, supply voltage and frequency all match, and the overall length fits the gap in the existing ductwork. Send the old unit's nameplate photograph and the duct size. We supply equivalents and we say plainly that they are equivalents, never that they are the original manufacturer's part.

Why is the fan noisier than the datasheet says?

Almost always because it is working harder than the design assumed. A fan pushed up its pressure curve gets louder. High air velocity in undersized duct adds its own noise, and a fan mounted rigidly to a light structure transmits vibration into the building. Flexible connectors at both ends and keeping duct velocity under 8 m/s solve most of it.

Next step

Let us size the right system for your building.

Share your floor area, roof height and what happens inside. A member of our engineering team will return a no-obligation quotation within 24 hours.

Call nowGet a quote