How Many Exhaust Fans Does a Factory Need? Sizing by Air Changes

Volume times air changes gives you the airflow. Then comes the part most specifications skip — the inlet area, without which the fans cannot deliver what they are rated for.

Published 5 November 2026 · Updated 5 November 2026 · Ayzair engineering team

Exhaust fan quantity is one of the few ventilation calculations that is genuinely simple. Work out the volume of the building, decide how many times an hour that volume should be replaced, multiply, and divide by the capacity of one fan. Four steps, no software.

What goes wrong is rarely the arithmetic. It is the two decisions either side of it: choosing an air change rate that suits the building rather than a number copied from a different one, and providing somewhere for the replacement air to come in. Get those wrong and a correctly calculated bank of fans still underperforms.

Step 1 — Volume, then air changes per hour

Volume is length by width by average clear height, in metres. Use the average height for a pitched roof rather than the ridge, or you will oversize.

Air changes per hour, or ACH, is how many times the entire air volume is replaced in an hour. The right figure depends on what happens inside, not on the size of the building. Heat, moisture, dust, fumes and the number of people all push it up.

Building typeAir changes per hour
Poultry shed, hot weather60
Greenhouse / polyhouse45
Commercial kitchen40
Factory / workshop20–30
Gym, sports hall, assembly hall20
Showroom / retail15–20
Warehouse / godown10–15

← Swipe the table sideways to see all columns

Step 2 — Divide by the capacity of one fan

Required airflow is volume multiplied by ACH, giving m³/h. Divide that by the rated airflow of the fan you intend to use and round up. Rounding down to save a fan is a false economy: the shortfall shows up on the hottest day of the year, which is the only day anyone judges the system.

Larger fans move air far more cheaply than small ones. A 1750 mm unit moves 68,000 m³/h on 1.5 kW, which is about 45,000 m³ per hour for every kilowatt. A 500 mm unit moves 5,000 m³/h on 0.25 kW, or 20,000 per kilowatt. Where the wall and the structure allow the bigger fan, it costs less to buy per unit of air and much less to run.

ModelSizeAir volumePowerAir per kW
Ayzair-17501750 mm68,000 m³/h1.5 kW45,300 m³/h
Ayzair-15301530 mm57,000 m³/h1.2 kW47,500 m³/h
Ayzair-13801380 mm44,500 m³/h1.1 kW40,500 m³/h
Ayzair-12201220 mm37,000 m³/h0.75 kW49,300 m³/h
Ayzair-11001100 mm34,000 m³/h0.55 kW61,800 m³/h
Ayzair-900900 mm27,000 m³/h0.37 kW73,000 m³/h
Ayzair-600600 mm8,000 m³/h0.25 kW32,000 m³/h

← Swipe the table sideways to see all columns

Step 3 — The inlet area, which is where most designs fail

A fan cannot exhaust air that cannot get in. If a shed is reasonably well sealed and the only deliberate opening is the fan itself, the fans spend their energy fighting the building instead of moving air, and delivered volume drops well below the rating on the plate.

The working rule is roughly one square metre of free inlet area for every 11,000 m³/h of installed exhaust. Free area means the actual hole, not the size of the louvre frame — a louvre is typically 50 to 60 per cent free area, and an insect mesh takes more again. Size the opening on free area and you will be right; size it on frame dimensions and you will be short by half.

The inlet should also be on the opposite side of the building to the fans. Inlet and exhaust on the same wall produces a short circuit: the air takes the easy path straight back out and the far end of the shed never sees fresh air, no matter how many fans are running.

Worked example: a 4,000 m² engineering workshop

The shed is 100 m by 40 m with an average clear height of 8 m, so the volume is 32,000 m³. It is a general engineering workshop with welding bays, which puts it at the upper end of the factory band — call it 25 air changes per hour.

32,000 m³ multiplied by 25 gives 800,000 m³/h. Using the 1380 mm fan at 44,500 m³/h each, that is 17.9 fans, so eighteen. Connected load is eighteen times 1.1 kW, or 19.8 kW.

Inlet area is 800,000 divided by 11,000, which is 73 m² of free area. Through a louvre at 55 per cent free area that means about 133 m² of opening — a band roughly 1.4 m high along the full hundred-metre length of the opposite wall. That number surprises people, and it is the single most common reason an otherwise correct installation disappoints.

Placement, and when exhaust is not the answer

Spread the fans along the wall rather than clustering them. An even line pulls air across the whole floor; a cluster pulls hard from the nearest few metres and leaves dead zones at the ends. Mount them high, because hot air collects at the roof and that is the air worth removing.

Exhaust ventilation replaces inside air with outside air. That is exactly what you want when the problem is heat from machines, fumes, moisture or stale air. It does nothing useful when the outside air is already hotter than the inside air — a sealed, shaded building at midday in the Gulf will get warmer, not cooler.

It is also the wrong tool when the complaint is that people at fixed workstations feel hot. Air changes fix the building; they do not produce the air movement across skin that makes a person feel cooler. That is a job for HVLS fans overhead, or a mobile fan at the workstation, usually alongside the exhaust rather than instead of it.

Send us the shed, we will send back the schedule

Length, width, average clear height, what happens inside, and roughly how much openable area the opposite wall has. An engineer will return fan model, quantity, placement, connected load and the inlet area you need — within one working day, free of charge.

Get a ventilation schedule

Answers

Related questions

Cannot find what you need? Call +91 80871 10156 or WhatsApp us — an engineer, not a call centre, picks up.

Ask on WhatsApp
Can I use fewer, larger fans instead of many small ones?

Usually yes, and usually you should. Large fans move more air per kilowatt and there are fewer motors to maintain. The limits are the structural opening the wall can take, and keeping enough fans spread along the wall that the airflow crosses the whole floor rather than one corner of it.

What if I cannot provide the inlet area the calculation asks for?

Then size the system to the inlet you can actually provide, because that is what will govern the result anyway. Tell us the real opening area and we will tell you the airflow it supports and what that means in air changes — an honest smaller number is more useful than an optimistic larger one.

Do exhaust fans cool a building?

They lower inside temperature towards the outside temperature, and no further. If it is 42 °C outside, exhaust ventilation cannot deliver 30 °C inside, and anyone who says otherwise is selling. Where the outside air is hot and dry, evaporative cooling can take the supply air below ambient; where it is hot and humid, it cannot, and air movement is the honest answer.

How high should the fans be mounted?

As high as the wall and the structure allow, since the hottest air sits under the roof. In a building with a tall pitched roof, ridge or high-level extraction removes the heat where it collects. In a low shed, high on the wall is close enough and much easier to maintain.